Brian Erga is a distinguished Senior Member of the Institute of Electrical and Electronic Engineers (IEEE), and active member of the IEEE Engineering in the Safety, Maintenance, and Operations of Lines Subcommittee (ESMO). Mr. Erga is currently chairman of the ESMO Induction Task Force and an active member of many IEEE, ESMO, Federal OSHA, ANSI, and ASTM committees, work groups and task forces. He is an active member of the NESC-C2 Subcommittee 8, responsible for NESC Part 4 "Work Rules."
Website URL: http://www.esci.net/index.html Email: This email address is being protected from spambots. You need JavaScript enabled to view it.

The minimum approach distance (MAD) is the closest distance a worker is permitted to approach an exposed energized conductor. When we think of MADs, we normally think of qualified electrical workers, and this discussion will cover what a MAD is, how it is developed, how it is to be applied and how it is often misapplied. There is also a second MAD for nonqualified electrical workers known as the 10-foot rule. Nonqualified electrical workers, subject to federal OSHA regulations, must remain a minimum of 10 feet away from any exposed energized conductors or equipment up to 50 kV, plus an additional 4 inches for every 10 kV above 50 kV.

The changes to Section 444.D, “Employee’s protective grounds,” and Section 445.A & B, “Protective grounds,” in the National Electrical Safety Code (NESC) 2012 were approved by NESC Subcommittee 8 after reviewing change proposals (CP) 3050 and 3051, respectively.

Friday, 16 December 2011 22:09

Your Personal Protective Grounding Process

In prior iP articles we have discussed effective methods of applying personal protective grounding to both overhead and underground electric utility systems. Proper application of the equipotential grounding method will ensure worker protection during an accidental re-energization or backfeed of the electric utility system. But what does your personal protective grounding practice do to reduce the hazards of induction? Is it possible your personal protective grounding practice is actually increasing the effects of induction? Let’s look at what we call induction, or what electrical engineers refer to as electric field induction and magnetic field induction.

This article is a continuation of the discussion published in the August 2011 issue of Incident Prevention, which covered personal protective grounding of overhead distribution and transmission systems. As with overhead grounding, there are three industry-accepted work methods that allow qualified employees to work with de-energized underground distribution cables and equipment. They are:
• Insulation
• Isolation
• Personal protective grounding, also known as equipotential grounding or EPZ

Personal protective grounding of overhead distribution and transmission lines and equipment is one of three industry-accepted work methods that allow qualified employees to work with de-energized lines and equipment. The other two methods are insulation and isolation. Following are descriptions of all three.

The wide variety of cover-up equipment currently available to the qualified electrical worker allows energized live-line work methods to be performed safety and productively. Cover-up equipment comes in several styles and voltage ratings for use in many different live-line applications. Flexible line hose, plastic guards and covers, rubber insulating blankets and sheathing allow the qualified electrical worker to install temporary insulation between themselves and energized conductors and devices.

OSHA 1910.269(m) – “De-energizing Lines and Equipment for Employee Protection” – covers de-energizing a section of an electric utility’s transmission and distribution (T&D) system, and the transfer of that section’s control from the system operator to the employee in charge. What does that mean? Simply put, paragraph (m) covers your company’s required written T&D switching and clearance procedure.

Tuesday, 15 February 2011 19:19

The Current State of FR Clothing

The current state of FR clothing for qualified electrical workers seems to be still greatly misunderstood. However, the current FR clothing requirement is very straightforward once you decide what side of the fence you’re on – the National Electric Safety Code (NESC) or the National Fire Protection Association (NFPA).

Many questions arise in the minds of electrical workers when the discussion turns to safely operating high-voltage, gang-operated disconnect switches while standing on the ground. These questions often include:

• Should the steel operating rod connecting the switch handle to the switch have an insulator (insulated insert)?
• Should the switch handle and operating rod be grounded to a ground rod?
• Should I wear rated rubber gloves?
• Should I be standing on a ground mat?

Friday, 01 October 2010 17:49

No Difference

A tree falls through a 7.2 kV, single-phase, overhead lateral, taking the tree, the phase conductor and common neutral to the ground. The electric utility sends a crew of qualified electrical workers to the site to re-install the overhead conductors.

The crew first goes to the upstream protective device (the cutout) protecting the lateral; let’s say it is Switch #1234. The crew will most likely find the cutout door open and the fuse blown. If the utility has a system operator on duty, the designated employee (normally the lead worker of the crew) will request permission from the system operator to open the upstream cutout, if it is not already open, and request a clearance from Switch #1234 to the end of the line.

Page 1 of 2

iP Contributing Authors

Subscribe-now-lg

FREE Subscription to iP Magazine.

We'll send you 6 issues a year at no charge!

Safety Management

Utility safety management is no easy job. Managing personnel, staying current on leg/reg issues, understanding record keeping processes and policy enforcement are only a few of the areas Incident Prevention provides in-depth coverage.

Read Safety Management articles

Personal Protective Equipment

OSHA requires the use of personal protective equipment (PPE) to reduce employee exposure to hazards. FR Clothing, Gloves, Head Protection, Eyewear and Protective Footwear are all PPE.  The  articles listed below discuss their proper use and maintenance. Attend iP Safety Conference & Expo to learn more about the latest PPE products.

Read Personal Protective articles

Tailgate Safety Topics

Tailgate meetings are a critical communication component of any strong utility safety program. Incident Prevention supplies the utility industry with topics for these important meetings. Each article can be printed out for use in the field or emailed to your crews.

Tailgate Safety Topic articles

Worksite Safety

Daily hazards face utility and contractor work crews. Understanding the risks involved, knowing the proper procedures, building a strong culture of open communication and constant awareness will prevent incidents. Our articles on aerial work, underground construction, grounding techniques, high-voltage risks provide utility workers a better understanding of the task at hand.  iP Safety Conferences are another great resource for understanding hazards.

Read Worksite Safety articles

Reader Profiles

Building an effective safety culture requires strong safety leadership.  The iP reader profiles features utility industry safety managers who know what it takes to overcome obstacles that brings their workers home each and every day.

Reader Profile articles

Leadership Development

As our current utility workforce retires, new utility safety leaders are coming onboard all of the time.  Incident Prevention is here to assist in the development of their leadership skills.  Managing people, understanding generational differences, building strong communications skills, establishing accountability are just a few of the subject areas covered in the magazine and at iP Safety Conferences.

Leadership Development articles

 

Equipment Operations

Safe equipment operations is required on every jobsite.  Utility work requires the use of cranes, derricks, buckets, trenchers, dozers and more.  Learn about the hazards associated with equipment operations in the articles featured below.

 Equipment Operations articles

Grounding

Grounding systems are designed so they provide the necessary safety functions. Understanding different grounding methods is critical for utility workers.  Incident Preventions relies upon industry experts to author these much needed articles.  For better insight on grounding methods used in the field you may want to attend iP Safety Conference and hear their in-depth presentations.

Read Grounding articles